Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL DBL STUD UNDER GARAGE GIRDER AT BEARING 2) STRAP GARAGE BEARING WALL (N.W. CORNER) INTERSECTION TO MIKEY BLOCK 3) JACUZZI TUB PLUMBING INCOMPLETE 4) MUST INSTALL ADDITIONAL VENT GARAGE TO ALL WITHIN 12" OF CEILING TO EXTERIOR 5) TRUSS BLOCKING NOT DONE 6) PLAN SHOWS SCISSOR TRUSSES CENTER OF HOUSE |
|
| 08/04/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS METER AND ELEC METER LOCATION NOT PER PLAN PLAN SHOWS FURNACE IN GARAGE PLAN CALLS FOR SCISSOR TRUSSES CENTER OF HOUSE TRUSS BLOCKING MISSING TOP & BOTTOM CHORDS 8' SPACING KITCHEN SINK LOCATION NOT PER PLAN ALSO DISHWASHER, RANGE, ETC ALL DWV PIPING TEST TO GO THRU ROOF WHAT IS PLB PIPING IN FLOOR W/ CAP FOR? INSTALL TUB AND CONNECT PLB INSTALL NUTS ON ALL THREAD HOLDING MAIN PAVEL TO WALL AND CUT OFF EXCESS INSTALL BANG PLATES PLB WITHIN 1 1/2 STUD FACE INSTALL BANG PLATES ELEC WITHIN 1 1/4" STUD FACE CANNOT LOCATE 22"X30" ATTIC ACCESS HOLE SECURE ELEC SUBPANEL TO WALL GROUND ALL METAL ELEC BOXES IN FOAM WALLS STRAP GARAGE BEARING WALL TO TO PLATE ON TOP OF MIKEY BLK WALL INST DBL STUDS UNDER GARAGE GIRDER TRUSS @ BEARING MAINTAIN MIN 1" CLEARANCE H20 HEATER FLUE PIPE TO COMBUSTIBLES SEPARATE NEUTRALS AND GROUNDS ELEC PANEL AND GRND BX PUT 2" SOIL PIPE VENT? BACK INTO WALL STOPPED INSP |