Permit: T04CM03431

Parcel: 116040220

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/15/2005 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
05/27/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST SUBMIT ASBUILT DETAIL RE: (REBAR NOT LAPPED WITH REBAR PROTRUDING FROM FTG AT JAMS AND OPENINGS) PER PREVIOUS REQUESTS
2) GROUT AT YOUR OWN RISK
05/24/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1ST LIFT JAMB REBAR NOT TIED INTO REBAR EMBEDDED IN FOUNDATION
2) DO NOT GROUT
3) MUST RECTIFY INITIAL PROBLEM FIRST
4) PER PREVIOUS PAPERWORK
05/12/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) VERTICAL REBAR CORNERS, JAMS AND EVERY 48" TO OVERLAP REBAR COMING OUT OF CONCRETE FOUNDATION (MOST REBAR WINDOW AND DOOR OPENINGS NOT TIED INTO FOUNDATION)
05/10/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HORIZONTAL REBAR WINDOW SILLS TO EXTEND 24" POST EACH JAM EACH SIDE EACH WINDOW OPENING
2) VERTICAL REBAR TO OVERLAP REBAR (SET IN CONCRETE FOUNDATION) MINIMUM 24" OVERLAP