Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2005 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
| 05/27/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST SUBMIT ASBUILT DETAIL RE: (REBAR NOT LAPPED WITH REBAR PROTRUDING FROM FTG AT JAMS AND OPENINGS) PER PREVIOUS REQUESTS 2) GROUT AT YOUR OWN RISK |
|
| 05/24/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1ST LIFT JAMB REBAR NOT TIED INTO REBAR EMBEDDED IN FOUNDATION 2) DO NOT GROUT 3) MUST RECTIFY INITIAL PROBLEM FIRST 4) PER PREVIOUS PAPERWORK |
|
| 05/12/2005 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) VERTICAL REBAR CORNERS, JAMS AND EVERY 48" TO OVERLAP REBAR COMING OUT OF CONCRETE FOUNDATION (MOST REBAR WINDOW AND DOOR OPENINGS NOT TIED INTO FOUNDATION) |
|
| 05/10/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HORIZONTAL REBAR WINDOW SILLS TO EXTEND 24" POST EACH JAM EACH SIDE EACH WINDOW OPENING 2) VERTICAL REBAR TO OVERLAP REBAR (SET IN CONCRETE FOUNDATION) MINIMUM 24" OVERLAP |