Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/21/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 6 X 6 POST BEARING ON WHAT? FLOOR IS COMPRESSING AT BASE OF POST 2) HANGERS FOR NEW AND EXISTING FRAMING NOT ON PLAN. USE CORRECT NAILS 3) PLAN CALLS FOR 3 BUILT UP BEAM MEMBERS, THAT MEANS TO SPLICES IT'S FROM SUPPORT TO SUPPORT 4) BUILT UP MEMBERS NEED A NAILING PATTERN TYING THEM TOGETHER OR ALL LOAD IS ON ONE MEMBER 5) NEED POST UNDER DBL GIRDER SOUTH WALL 6) OUTLET AT COUTNER, IF OVERHANG IS MORE THAN 6" OUTLET CANNOT BE UNDER COUNTER |
|
| 04/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE FIREBLOCK AT NITCH 2) PROVIDE CRIPPLE AT DBL GRD AT SOUTH SIDE WALL 3) STRAP BEAM TO MAKE POSITIVE CONNECTION |
|
| 04/20/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED STUDS UNDER DBL GIRDER SOUTH WALL AND CRIPPLES 2) 2" TRAP ARM NOT ALLOWED AT LAV. AND NAIL PROTECT 3) GROUND METAL BOX AT PATIO 4) OK TO INSULATE 5) INSPECTED FLOOR JOISTS OK |