Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM03412
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/31/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TO CLEAR FOR POWER, TWO ITEMS REQUIRED FOR FINAL ONCE TEP ENERGIZED CALLFOR POWER CHECK FOR INSPECTIONS OF SMOKE DETECTORS, ARC FAULT SYSTEMS, GFI CIRCUITS FENCE REMOVAL SECTION WILL NOT WORK CLEARANCE DOES HAVE TO BE THERE ALL THE TIME, WHAT WILL WORK IS THIS INSTALLATION 36" ARE NEEDED. |
|
10/25/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : CORRECTIONS NOT MADE YET. |
|
10/18/2005 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
10/16/2005 | ELECTRIC - FINAL | Denied | NO MAIN BREAKERS NOR WIRING TERMINATED AT SERVICES SERVICE REQUIRES 3' OF CLEARANCE IN FORNT OF PLAN SHOWS 2/0 AT GROUNDING SYSTEM NOT # 4 PLANS SHOWS UG SE NOT OVERHEAD. DISCONNECTS FOR AC TO BE SECURES & NOT IN FRONT OF UNITS. INSIDE PANELS TO BE MARKED( PERMANENTLY) NEED FUSES FURNACE SD' ON PLAN AT TOP OF STAIRS MISSING |
|
10/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NEED APPROVED ELECT PLANS ONSITE IN ORDER TO MAKE INSPECTION. |