Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM03412

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2005 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
01/06/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/*PLEASE HAVE ENGINEER OF RECORD MR. JEROME MCGETRICK IS A LETTER CLAIFYING THE LANGUAGE OF NOTE 15 AT PLAN SHEET EZ. WHAT EXACTLY DOES HE MEAN BY "SO ALL UNITS SOUND ALARM WHEN ANY DETECTOR IS IN ALARM" DOES HE MEAN SMOKE ALARM UNITS LOCATED WITNIN EACH APARTMENT UNIT ONLY-OR-ALL APARTMENT UNITS
12/22/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PLEASE EXPLAIN AND PROVIDE PROOF FOR THE FOLLOWING: ALL BEDROOMS CIRCUITS MUST BE ON ARC FAULT CIRCUIT BREAKERS INCLUDING ALL LIGHTING AND OTHER 120/240 V APPARTATUS ( SMOKE DETECTORS )
2) SPECIFICATIONS REQUIRE ALL SMOKE DETECTORS TO BE INTERCONNECTED TO ALARM SIMULTANEOUSLY. THIS MEANS ALL SMOKE ALARMS IN THE BLDG
3) PROVIDE MANUFACTURERS PROOF ALLOWING THE RECESSED LIGHT FIXTURE BALLASTS TO BE MOUNTED ON COMBUSTIBLE SURFACE
4) IS THERE A CENTRAL FIRE ALARM SYSTEM ?