Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM03406
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2004 | FRAMING | Approved | IVRS - Inspection :* | |
11/22/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXTEND SHEAR WALL TO TOP PLATE BEHIND KITCHEN 60 FEET 2) NAIL UP LOOSE WIRE IN KITCHEN SOFFIT 3) TRUSSES MISSING BRACING ABOVE STAIRS 4) SHEARWALL #1 BEDROOM 2 NOT NAILED AT BOTTOM PLATE AT 12" ON CENTER ALSO AT BATHROOM |
|
11/02/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NAIL PROTECT ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD 2) NO TEST ON DWV'S 3) GAS GAUGE FACE MISSING AND BROKEN 4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE 5) REPLACE STUDS AT KITCHEN SHEAR WALL 6) REPAIR SHEARWALL AT KITCHEN 7) HORIZONTAL WATER LINE RUNS REQUIRE 1 1/2" CLEARANCE FROM EDGE 8) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT FAU B-VENT 9) PROVIDE OPTION FOR VAULTED CEILING IN MASTER B/R |