Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM03406

Parcel: 140323800

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03406

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2004 FRAMING Approved IVRS - Inspection :*
11/22/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) EXTEND SHEAR WALL TO TOP PLATE BEHIND KITCHEN 60 FEET
2) NAIL UP LOOSE WIRE IN KITCHEN SOFFIT
3) TRUSSES MISSING BRACING ABOVE STAIRS
4) SHEARWALL #1 BEDROOM 2 NOT NAILED AT BOTTOM PLATE AT 12" ON CENTER ALSO AT BATHROOM
11/02/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NAIL PROTECT ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD 2) NO TEST ON DWV'S 3) GAS GAUGE FACE MISSING AND BROKEN 4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE 5) REPLACE STUDS AT KITCHEN SHEAR WALL 6) REPAIR SHEARWALL AT KITCHEN 7) HORIZONTAL WATER LINE RUNS REQUIRE 1 1/2" CLEARANCE FROM EDGE 8) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT FAU B-VENT 9) PROVIDE OPTION FOR VAULTED CEILING IN MASTER B/R