Permit: T04CM03403

Parcel: 140323120

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM03403

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2004 BUILDING - FINAL Approved IVRS - Inspection :*
1) NOTE OF RECORD: AS PER PHONE CONVERSATION WITH J. RIVA HE DID APPROVE AND IVR INSPECTION 01015, NOT SIGNED OFF ON CARD
12/13/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #1, #2, #3, #5 AND #6 FROM INSPECTION DATED 12/10/04 NOT DONE
12/10/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ADDRESS ON PANEL
2) SEAL KNOCKOUT AT BOTTOM OF PANEL
3) DISCONNECT WHIP NOT SCURED
4) SMOKE DETECTOR IN FRONT BEDROOM DOES NOT ACTIVATE REST OF SMOKE DETECTORS
5) PROVIDE MANUFACTURERS INSTALL INSTRUCTION FOR ? SYSTEM BEING INSTALLED IN ATTIC
6) INSULATE ENTIRE COPPER LINE TO UNIT IN ATTIC
7) REST OF HOUSE OK
2) SEAL KNOCKOUT AT BOTTOM OF PANEL
3) DISCONNECT WHIP NOT SECURED
4) SMOKE DETECTOR IN FRONT