Permit: T04CM03403

Parcel: 140323120

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03403

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2004 FRAMING Approved IVRS - Inspection :*
10/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 2) TRANSAM WINDOW IN FRONT NOT DONE 3) SEAL LATH MOISTURE BARRIER FROM INSIDE 4) TRANSFER GRILL TO OUTSIDE NOT DONE 5) TOILET IN HALL BATH DOES NOT HAVE THE 15" FROM OBSTRUCTION 6) REMOVE SCREEN FROM DRYER VENT T-TOP 7) WATER LINE IN LIVING ROOM DOES NOT HABE THE 1 1/2" CLEARANCE FROM EDGE HORIZONTALLY 8) REPLACE CRIPPLE UNDER MASTER WINDOW 9) LEAK AT MASTER LAB VENT 10) PROVIDE STUD SHOE AT 2 X 6 WALL MASTER BATH 11) RE-TEST PLUMBING 12) MASTER TUB DRAIN LEAKING 13) FAU MISSING B-VENT
10/18/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DBL SHEARWALL 1 DOES NOT EXTEND TO DBL TOP PLATE 5/D3 NOT PER PLAN. PROVIDE CITY OF TUCSON, ARCHITECT APPROVED REPAIR 2) HOLE IN LATH BY COMBUSTION AIR 3) DBL TOP PLATES CUT ON DBL #1 SHEARWALL. PROVIDE REPAIR 4) FIRBLOCK MISSING M/CLOSET 5) NO PLUMBING PLAN 6) GAS LINE NOT SUPPORTED PER UPC 1/2" 6' ON CENTER