Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 10/29/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 1 1/2" CLEARANCE REQUIRED BETWEEN REBAR AND PLUMBING 2) ALL PLUMBING THAT MAY CONTACT CONCRETE MUST BE IN SLEEVES OR WRAPPED 3) REBAR CANNOT BE IN CONTACT WITH SOIL 4) NO UFER |
|
| 10/28/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |