Permit: T04CM03397

Parcel: 140383200

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/13/2004 FRAMING Approved IVRS - Inspection :*
12/10/2004 FRAMING Partial Approval IVRS - Inspection :*
1) 2" DIRY ARM NOT ALLOED ON LAV
2) WATER LINES OK
3) RETEST DWV'S
4) SEE #4 AND #8 INSPECTION DATED 12/08/04
5) FIRE BLOCK F/P AREA
12/08/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KING STUD MISSING AT SGD OPENING
2) PROVIDE 12" CLEARANCE FROM CAN LIGHTS FOR WATER LINES
3) BLOWN FIRE BLOCK AT MASTER BATH
4) CLIP 2 X 6 STUD AT SHEAR TRANSFER MASTER TOILET
5) OVER SPAN AT BEDROOM 2
6) REPAIR ARMA FLEX IN ATTIC SPACE
7) NOT ALLOWED TO USE PLUMBERS TAPE TO SUPPORT AB'S
8) 1 1/2 DIRTY ARM EXCEEDS 42" AT HALL BATH
9) REMOVE SCREEN FROM DRYER VENT
10) STOPPED INSPECTION
12/03/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ENTRY TOWER FRAMING NOT PER PLAN
2) COLUMN TRUSS MUST BEAR ON DBL TOP PLATES
3) NAIL PROTECT ELECTRIC WITHIN 1 1/4' FROM EDGE OF STUD
4) FIRE BLOCK MISSING AT KITCHEN WALL
5) NO TEST ON DWV'S
6) STOPPED INSPECTION