Permit: T04CM03397

Parcel: 140383200

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/10/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/19/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) PARTIAL PENDING PLAN AND CALC REVISIONS MUST HAVE BY INTERMEDIATES
11/18/2004 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
11/16/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) EXCEPT FRONT ENTRY
2) COLUMN TRUSS NOT BEARING ON DBL TOP ?, SEE LAST INSPECTION
3) PROVIDE CAP AT VERTICAL JOINTS ROOF SHEATHING
11/12/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CHECK FOR OVERSPAN
2) WALLS NOT CABIN TIED. NEED TO BE STRAPPED
3) NAIL PROTECT ELECTRIC AND PLUMBING FROM OUTSIDE
4) LET IN BRACES REQUIRED 2 NAILS ON ENDS
5) BOX COLUMN NOT SHEARED
6) PROVIDE TOWER FRAMING DETAIL
7) TRUSS DRAWINGS, DO NOT MATCH PLAN APPROVAL DATES
8) NO BRACING
9) TOP PLATES BOWED AT HEADERS
10) SHIM 3 POINT BEARING TRUSSES
11) H. D. AT BATH REMOVE-ADD STUD AND INSTALL
12) STOPPED INSPECTION
11/10/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) OVER SPAN AT SHEAR #6 AT GARAGE
2) COMPLY WITH DETAIL 6/DT1
3) WINDOW AT ENTRY HEADER CALLS FOR 2-2 X 8'S
4) 4 JAMB STUDS REQUIRED AT GARAGE ENDS
5) PROVIDE DETAIL FOR KNEE WALL AT ENTRY
6) PROVIDE ROOF ACCESS
7) STOPPED INSPECTION