Permit: T04CM03393

Parcel: 113010540


Addresses:

1301 E ALLEN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL IS NOT CORRECTLY IDENTIFIED (BRANCH CKTS)
2. STILL NEED PROPER LUG FOR CONTRACTOR ENCLOSURE GROUND.
3. STILL HAVE OPEN HOLES IN EXTERIOR BOXES.
4. CCTV TRANSFORMER CORD STILL IN WALL.
5. NEED TO PAY REINSPECTION FEE BEFORE FINAL APPROVAL.
6. USE PROPER SIZE CONNECTOR FOR TOP OF LOW VOLTAGE BOX UNDER PANEL.
06/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TRANSFORMER WIRE FOR CCTV CAN'T PASS THROUGH WALL
2. INSTALL FAN TRIM
3. DO NOT DOUBLE CONDUCTORS TO BREAKERS
4. MAX. 15 AMP. ON 14 GA CONDUCTOR.
5. CORRECTLY IDENTIFY ALL CKTS IN PANEL DIRECTORY.
6. USE LISTED LUG TO GROUND CONTACTOR ENCLOSURE.
7. INSTALL BLANK COVER ON LOW VOLTAGE BOX.
8. LOW VOLTAGE WIRING AND POWER/LIGHT CKTS ARE NOT ALLOWED TO OCCUPY SAME ENCLOSURE.
9. ALL EXTERIOR BOXES NEED TO BE WEATHERPROOF, HAVE COVERS INSTALLED AND OPEN K.O HOLES CLOSED OFF.