11/23/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/16/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)MAINTAIN WORKING CLEARENCES AT AC DISCONNECTS AND SERVICE- OUTSIDE 2)DISCONNECTING MEANS NOT TO BE ON ACCESS ABOVE PANELS 440.14 3)LABEL PANEL COVERS & BREAKERS WITH CIRCUITS 4)BLANK OFF BOXES 5)BONDING JUMPER TO BE SIZED PER 250.102 & 250.66 6)WEATHER PROOF COVER TO BE WEATHER OR NOT PLUGED IN |