Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM03383

Parcel: 12108001B


Addresses:

6291 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM03383

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/16/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/1)MAINTAIN WORKING CLEARENCES AT AC DISCONNECTS AND SERVICE- OUTSIDE 2)DISCONNECTING MEANS NOT TO BE ON ACCESS ABOVE PANELS 440.14 3)LABEL PANEL COVERS & BREAKERS WITH CIRCUITS 4)BLANK OFF BOXES 5)BONDING JUMPER TO BE SIZED PER 250.102 & 250.66 6)WEATHER PROOF COVER TO BE WEATHER OR NOT PLUGED IN