Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 11/16/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/1)MAINTAIN WORKING CLEARENCES AT AC DISCONNECTS AND SERVICE- OUTSIDE 2)DISCONNECTING MEANS NOT TO BE ON ACCESS ABOVE PANELS 440.14 3)LABEL PANEL COVERS & BREAKERS WITH CIRCUITS 4)BLANK OFF BOXES 5)BONDING JUMPER TO BE SIZED PER 250.102 & 250.66 6)WEATHER PROOF COVER TO BE WEATHER OR NOT PLUGED IN |