Permit: T04CM03365

Parcel: 140107210

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/20/2004 FRAMING Approved IVRS - Inspection :*
10/19/2004 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) NO GAS BOND 2) #2 SHEAR BLOCK MISSING AT GAS LINE 3) SHEAR BLOCKING PANEL DAMAGED AT DINING ROOM 4) NAIL PROTECT PLUMBING WITHIN 1 1/2" OF STUD SURFACE 5) DBL TOP PLATES NOTCHED GREATER THAN 40 PERCENT-INSTALL FHA STRAPS AT CONDENSATE LINES 6) ANCHOR BOLT MISSING NORTH WALL 7) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 8) LAV TRAP ARM MUST BE SAME SIZE AS TRAP NOT 3" MAX 1 1/2" 9) LEAK AT CLEANOUT 10) AC WIRES NOT OUTSIDE 11) STOPPED INSPECTION, TOO MANY ITEMS 11) LATH WIRE MISSING MANY PLACES