Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/18/2004 FRAMING Approved IVRS - Inspection :*
11/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BANG PLATE-ABS AT 2ND FLOOR CLOSET, PLASTIC PIPES AND CONDENSATE LINE ON EAST GARAGE TOP PLATES
2) SEE NUMBERS 3, 4, 6, 7, 13
3) NEED PLANS AND PERMIT ON SITE
11/10/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) ABS NOT CONNECTED ABOVE SHOWER
2) BANG PLATE ALL PLUMBING WHERE NEEDED
3) PROVIDE STEAMER SPECS
4) WHERE DID HOT WATER HEATER MOVE TO?
5) FRAME DOES NOT GET INSPECTED UNTIL ALL INTERMEDIATES PASS
6) FINISH MESH AT WINDOWS/DOORS
7) SEAL PLUMBING PROTRUSIONS AT WEST GARAGE WALL
8) NEW AIR HANDLER DISCONNECT NOT IN YET
9) PROTECT HVAC LINES AT PLATES
10) PROVIDE NEW AIR HANDLER SPEC. SHEET (INSTALLATION INSTRUCTIONS)
11) CONDENSATE LINE NOT INSTALLED
12) BLOCK ALL DUCT BOOTS ON 3 SIDES
13) DO NOT INSULATE OR SHEETROCK BEFORE ALL INTERMEDIATES PASS
10/07/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) ROOF SHEATHING OK TO COVER 2) LEDGER CLIPS AND ROOF PARAPET OK TO COVER