Permit: T04CM03338

Parcel: 11451216C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2005 ELECTRIC - FINAL Approved
01/24/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK FOR TEMP C OF O PLEASE ROLL OVER BOND. 1) WAITING ON PLAN REVISIONS
01/21/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*1) LIGHTING PLANS AND FIXTURE SCHEDULE DO NOT REFLECT WHAT IS INSTALLED 2) SEAL WALK IN BOX CONDUITS PER 300.7. 3) WALK IN CONTROLER TO HAVE LOCKABLE DEVICE FOR DISCONNECTING MEANS. 4) PANELS TO BE MARKED ON OUTSIDE OF COVER AND CIRCUIT DRECTORY TO BE PERMANENT.
ROOF: 1) SUPPORT SEALTITE/ LIQUID TITE ? OFF OF ROOF 2) USE LISTED WEATHER PROOF FITTINGS 3) HOOK UP A/C UNIT.