Permit: T04CM03338

Parcel: 11451216C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/24/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/13/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) WHEN SUP?? ELECTRIC IS TO BE CONNECTED AT BOTH ENDS 300.11. 2) FINISH CAN SUPPORT WIRES. 3) UNGROUNDED CONDUCTOR TO BE COLOR CODED PER 210.5 (C) CITY REQUIREMENTS
01/12/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/OK JUNCTION BOXES TO CLOSE. OK 2X4 LAY-INS 1)SUPPORT WIRES NEEDED ON BOXES & FIXTURES IN CEILING 2)BOXES AND CANS TO BE FLUSH WITH COMBUSTABLE TILE SURFACE 370.20/314.20 3)SUPPORT VDV CABELING AS PER CODES 725.6 4)SERVICE BONDING TUBS AS PER 250-94/250.92 5)BONDING JUMPERS TO BE SIZED PER 250-102 & 250-66
11/15/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*