Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2005 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 01/13/2005 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* 1) WHEN SUP?? ELECTRIC IS TO BE CONNECTED AT BOTH ENDS 300.11. 2) FINISH CAN SUPPORT WIRES. 3) UNGROUNDED CONDUCTOR TO BE COLOR CODED PER 210.5 (C) CITY REQUIREMENTS |
| 01/12/2005 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :*/OK JUNCTION BOXES TO CLOSE. OK 2X4 LAY-INS 1)SUPPORT WIRES NEEDED ON BOXES & FIXTURES IN CEILING 2)BOXES AND CANS TO BE FLUSH WITH COMBUSTABLE TILE SURFACE 370.20/314.20 3)SUPPORT VDV CABELING AS PER CODES 725.6 4)SERVICE BONDING TUBS AS PER 250-94/250.92 5)BONDING JUMPERS TO BE SIZED PER 250-102 & 250-66 |
| 11/15/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |