Permit: T04CM03331

Parcel: 140375620


Addresses:

7052 S PETREL LN

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/22/2005 FRAMING Approved IVRS - Inspection :*
02/18/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/17/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO POST TENSION TAG
2) PAINT IRRIGATION PVC
3) FINISH GRADE AROUND HOUSE NOT PER CODE
4) B1 TRUSS REPAIR NOT APPROVED BY CITY OF TUCSON
5) STOPPED INSPECTION
02/15/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLAN OR PERMIT
2) EXPOSE REPAIR ON BOTH SIDES
01/26/2005 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
No plan/permit on site
01/12/2005 FRAMING Partial Approval IVRS - Inspection :*
1) NO REPAIR DONE AT KITCHEN WALL DBL TOP PLATE
2) NO CITY OF TUCSON APPROVED REPAIRS FOR KITCHEN WALL TRIPPLE GIRDER OR B1 TRUSS
01/11/2005 FRAMING Partial Approval IVRS - Inspection :*/1)MECHANICAL CHASE NOT FIRE BLOCKED 2)FRAMING PARTIAL PENDING CITY OF TUCSON APPROVAL FOR TRIPPLE GIRDER, B1 TRUSS AND KITCHEN WALL REPAIR DBL TOP PLATE
01/07/2005 FRAMING Partial Approval IVRS - Inspection :*
1) DWV'S WATER LINES OK
2) SEAL ALL PENETRATIONS FROM 1S T TO 2ND FLOOR AND INTO ATTIC SPACE
2) WATER LINE AT DINING AREA BELOW CEILING LINE NOT SECURED
3) NAIL PROTECT T & P LINE
4) FIREBLOCK MECH CHASE INTO ATTIC
5) PARTIAL FRAMING PENDING CITY OF TUCSON STAMP OF APPROVAL, OK TO INSULATE, LEAVE ACCESS TO ITEMS NOT INSPECTED
01/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER LEAKS AT MANIFOLDS
2) PROVIDE ENGINEERING FOR SHEAR TRANSFER WALL AT KITCHEN
3) SEAL ALL PENETRATIONS
4) WATER LINE BELOW CEILING NOT SECURED AT DINING AREA
5) PROVIDE GIRDER AND TRUSS REPAIR. SEE LAST INSPECTION
01/05/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER LEAK AT LAUNDRY ROOM CEILING
2) PROVIDE 3 PLY GIRDER REPAIR
3) B1 TRUSS BOTTOM CHORD CRACKED, REQUIRES ENGINEER APPROVAL
4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND TO ATTIC SPACE
5) PROVIDE ENGINEERING FOR DBL TOP PLATE SHEAR TRANSFER WALL AT KITCHEN