Permit: T04CM03322

Parcel: 11627504A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/20/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)SOIL WATER TEST IS OK 2)NOTE: CONTRACTOR SHALL SEAL ALL ROOF & DECK DRAINS WHEN THE CONCRETE HAS DRIED? DUE TO TEST
12/15/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)HUSKEY BANDS ARE LEAKING AND REQUIRE 80 LBS OF TORK WITH PROPER TORK WRENCH.
12/14/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY FOR INSPECTION
12/14/2004 PLUMBING - FINAL Denied IVRS - Inspection :DENIED. 1) DO NOT CALL UNTIL PLUBS CONTRACTOR HAS MADE HIS CORRECTIONS.
12/10/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL NOT LOCATE A FERNCO? REDUCER COUPLING WITHIN THE STRUCTURE 2)SHALL PROVIDE APPROVED TRANSITION COUPLING FROM PLASTIC TO C.I. 3)SPECS CALL FOR HUSKEY BANDS COUPLINGS 4)RE TEST SYSTEM