Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/19/2004 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 10/13/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |