Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/30/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) NOTE: NO INSPECTION. COULD NOT REACH JEFF MATHEWS 4 X. 2) MR. MATTHEWS QUESTIONING LISTINGS. WILL LEAVE MESSAGE ON IVR SYSTEM. NEC 110.3 EXAMINATION OF EQUIPMENT. 670 INDUSTRIAL MACHINERY. 670.3 NEED PERMANENT METALIC ENGRAVED DATA TAG. ALL EQUIPMENT MUST BE LISTED BY U.L. OR EQUIVALENT | |
| 07/26/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :LIQUID TIGHT FLEX MET COND TO BE SUPPORTED @ 12" FROM BOX AND EVERY 4 1/2' THEREAFTER PLEASE CORRECT ADDRESS WILL NEED ALL EQUIPMENT LISTED |