Permit: T04CM03266

Parcel: 141110310

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/12/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/30/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) NOTE: NO INSPECTION. COULD NOT REACH JEFF MATHEWS 4 X. 2) MR. MATTHEWS QUESTIONING LISTINGS. WILL LEAVE MESSAGE ON IVR SYSTEM. NEC 110.3 EXAMINATION OF EQUIPMENT. 670 INDUSTRIAL MACHINERY. 670.3 NEED PERMANENT METALIC ENGRAVED DATA TAG. ALL EQUIPMENT MUST BE LISTED BY U.L. OR EQUIVALENT
07/26/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :LIQUID TIGHT FLEX MET COND TO BE SUPPORTED @ 12" FROM BOX AND EVERY 4 1/2' THEREAFTER
PLEASE CORRECT ADDRESS
WILL NEED ALL EQUIPMENT LISTED