Permit: T04CM03264

Parcel: 107123350


Addresses:

85 E LAGUNA ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/31/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/22/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* "B" WATE VENT ASSY. REMOVE 3" B-1 ADJ ? CONTINUE 3" SINGLE WALL PIPE CUP INTO Y FITTINGS. CANNOT TRANSITION INTO B-1, THEN BACK TO SINGLE WALL PIPE. COND. DRAINS 3/4" PVC OPEN VENT FOLLOWS TRAP, NOT AHEAD OF IT. MIN/MAX FUSE SIZE ON CONDENSERS. 20 AMP. ( ALL UNITS NEED FUSES)