Permit: T04CM03249

Parcel: 13001010A


Addresses:

1519 S TUCSON BL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03249

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2005 FRAMING Approved IVRS - Inspection :*
01/31/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
01/21/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) BANG PLATE ALL PIPES AND WIRES
2) ANCHOR BOLTS REQUIRED 12" FROM EACH END OF PLATE SPLICE AND 6' ON CENTER THERE AFTER
3) CONNECT EXHAUST FAN CENTER BATH
4) NEED DRAIN WASTE AND VENT SYSTEM H20 TESTED
5) 50 PSI ON H20 LINES OR NORMAL WORKING PRESSURE, H20 ON
6) NEED 110 OUTLET FOR RANGE
7) BLOCK ALL MECHANICAL DUCTS
8) ALL CLOSET LIGHTS, COMPLY WITH CODE 12" ARC. FROM SELF, 6" ARC. FOR RECESSED, OR FLOURESCENT LIGHT
9) SECURE ALL INTERIOR BOTTOM PLATES
1) CHECK MANUFACTURERS BOOK FOR HOLE, SIZE AND DISTANCE IN TJI ?
11/30/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) OK TO INSTALL STUCCO MESH
2) FRAMING TO BE APPROVED AFTER ALL OTHER TRADES ARE COMPLETED