Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM03247
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/09/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/CORRECTIONS: 1)THE LARGER RECESSED CAN LITE FIXTURES ARE NOT PROPERLY SECURED TO CEILING GRID. USE CORRECT HANGERS. 2)NE CODE ARTICLE 300 PROHIBITS THE USE OF THE EMT SYSTEM TO SUPPORT THE M.C. FIXTURE WHIPS. CLAMP OR HANG TO/FROM TRUSSES. |