Permit: T04CM03232

Parcel: 112018000

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/21/2005 FRAMING Approved IVRS - Inspection :*
04/11/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PARTIAL FOR LAGS AT PATIO
04/05/2005 FRAMING Partial Approval IVRS - Inspection :*
1) FRAMING PARTIAL PENDING PATIOS
03/31/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE BLOCKING MISSING THROUGHOUT HOUSE TO INCLUDE PENETRATIONS FROM 1ST TO 2ND FLOOR
2) NAIL PROTECT CONDENSATE LINE
3) ROOFING MATERIAL TO CLOSE TO B-VENT
4) REMOVE SCREEN FROM DRYER VENT T-TOP AND DRYER VENT CRUSHED
5) FIREBLOCK CHASES
6) PROVIDE 30" OF WORKSPACE IN FRONT OF UNIT AND HEAD ROOM
7) DRYER VENT EXCEEDS THE 25 FT ALLOWED BY CODE
03/04/2005 FRAMING Not ready for Inspection IVRS - Inspection :*