Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/28/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOTH UNITS INCORRECTLY FUSED 1. MAX. FUSE SIZE 30 AMPS - UNIT FUSED AT 35 AMPS. 2. WESTSIDE UNIT - PVC CONDENSATE PIPE NEEDS TO BE PAINTED. |
|
| 07/19/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANNOT RUN HIGH/LOW VOLTAGE IN SAME CONDUIT, SEAL TITE, ETC... |