Permit: T04CM03199

Parcel: 137060150

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE
03/28/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) STUBB OUT FOR 2" TRAP ARM SHALL BE 2" NOT 1 1/2 AND A 2" P-TRAP SHALL BE INSTALLED ON FINISH. 2) SHALL BRACE & STRAP ALL HORIZONTAL VENTS ABOVE CEILING. 3) DWV SOIL WATER TEST IS OK. 4) OVERHEAD WATER DISTRIBUTION IS OK