Permit: T04CM03187

Parcel: 122173100

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/24/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*CORRECTONS MADE OK
OK TO COVER ALL AREAS
02/23/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORTS REQUIRED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
2. SUPPORT DOES NOT MEAN PASSING THRU HOLES IN THE JOIST REQUIRE STRAPS OR HANGERS.
3. CONDENSATE PIPING TO BE INSTALLED IN WORKMANSHIP LIKE MANNER WITH 2% GRADE TO LAV. SUPPORT TO TABLE 3-1 94 UPC