Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 10/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECTLY IDENTIFY PANEL DIRECTORY'S 2. INSTALL PROPER WATTAGE BULBS IN HOODS, FIXTURES 3. ALL J-BOXES TO BE GROUNDED 4. WIRING BETWEEN BUILDINGS FOR FIRE ALARM AND HOUSE LIGHTING TO BE ADDED TO PERMIT/SCOPE OF WORK 5. INSTALL LATCH FOR SPRINKLER ENCLOSURE. 6. HAVE OPEN WIRING THROUGH WALL AT LAUNDRY. 7. FIRE ALARM WIRINIG TO BE SEPARATE FROM POWER AND LIGHT CONDUCTORS AND J-BOX WITH FIRE ALARM TERMINATIONS TO BE IDENTIFIED. OK TO OCCUPY |
|
| 10/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |