Permit: T04CM03187

Parcel: 122173100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORRECTLY IDENTIFY PANEL DIRECTORY'S
2. INSTALL PROPER WATTAGE BULBS IN HOODS, FIXTURES
3. ALL J-BOXES TO BE GROUNDED
4. WIRING BETWEEN BUILDINGS FOR FIRE ALARM AND HOUSE LIGHTING TO BE ADDED TO PERMIT/SCOPE OF WORK
5. INSTALL LATCH FOR SPRINKLER ENCLOSURE.
6. HAVE OPEN WIRING THROUGH WALL AT LAUNDRY.
7. FIRE ALARM WIRINIG TO BE SEPARATE FROM POWER AND LIGHT CONDUCTORS AND J-BOX WITH FIRE ALARM TERMINATIONS TO BE IDENTIFIED.

OK TO OCCUPY
10/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*