Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) NOTE: INSTALL WARNING 2) RIBBON IN DITCH 3) MINIMUM 12" ABOVE ALL SERVICE CONDUCTORS |
|
| 04/13/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* LUG WHERE GROUND ELECTRODE CONDUCTOR COME INTO CABINET, MUST BE BOLTED & NUT ATTACHED ALSO SCRAP PAINT BEHIND LUG. |