Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*HAVE ELECTRICAL PLANS ON SITE USE PROPER TOOL FOR CRIP SLEEVES NEC 110.14 SPACE OUTLETS PER CODE NEC 210.52 GROUND METAL BOXES NEC. 314.4 INSTALL NAIL PLATES AS NEEDED NEC 300.4 |