Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ACTIVATE GARAGE OUTLETS. 2) INSTALL BACKFLOW PREVENTER VALVES |
|
| 02/04/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED GAS PRESSURE TEST ON NEW PIPING |
|
| 02/01/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL NEW GAS PIPING MUST BE PRESSURE TESTED 2) PLUS CIRCLED ITEMS ABOVE: WINDOW NOT ALLOWED 3) H20 HTR TEMP, PRESSURE RELIEF HME, MUST GO TO OUTSIDE OF BLDG |
|
| 12/22/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PLEASE LOCATE H PAHD 22 HOLDING AT GARAGE FRONT 2)PLAN DOESN'T SHOW ROOM TYPE (DOOR, WINDOW) WHAT TYPE ROOM IS ON THE OTHER SIDE, DOOR TO BE SOLID CORE, OR STEEL (SELF CLOSING) (SEE CITY ADMENDMENTS) WINDOW IS NOT ALLOWED 3)WATER IRON PIPES, IRON PIPES BELOW SLAB TO BE WRAPPED, GALVINIZED NOT AN APPROVED PROTECTION 4)IF PIPES ARE GAS LINES THEY CONNOT BE BELOW SLAB 5)YOU HAVE A H20 HTR TEMP, PRESS, RELIEF HME, MUST GO TO OUTSIDE OF BUILDING 6)WOOD WALL BETWEEN HOUSE & GARAGE TO BE 1/2" DRY WALL 7)E 3801.9 YOU NEED MINIMUM 1 125 VOLT G.F.C.I. PROTECTED OUTLET IN GARAGE 8)FINISH ELEC, FOR AUTO DOOR |