Permit: T04CM03162

Parcel: 127090080

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM03162

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/30/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*PARTIAL APPROVAL. 1) MISSINGBUSHING FOR BONDING ON A/C UNITS, 2)TIGHTEN BUSHINGS. HP,3,9,10 111,8,4,5,
09/28/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/OK TEMP C OF O - COMPLETE #6,, 8 & 9 BY 10-01-04 SUBJECT TO STEVE LONG
09/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) ACCESS REQUIRED FOR ELECTRICAL-WATER COOLER PLATES 2) CONDUCTOR COLORS TO BE AS PER CITY AMENDMENTS 3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING-NON COMBUSTIBLE FLUSH WITH COMBUSTIBLES 4) BOXES TO BE GROUNDED NOT USING SHEET METAL THREAD SCREWS 5) BOND BUSHINGS FOR CONCENTRICS OVER 250 VOLTS 6) MAINTAIN WORKING CLEARANCE IN FRONT OF A/C 7) PLANS ARE STAMPED AFTER 7/1/04-WORK IS TO BE AS PER 2002 NEC 8) COVERS ON ROOF TO BE WEATHER PROOF OR NOT PLUGED IN 406.8 9) A/C DISCONNECTS NOT ALLOWED ON ACCESSIBLE PANELS 440.14
09/13/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/1)FINISH ELECTRIC?
SUBJECT TO STEVE LONG FOR STOCKING