Permit: T04CM03162

Parcel: 127090080

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T04CM03162

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2004 ELECTRIC - UFER Approved IVRS - Inspection :*
09/10/2004 ELECTRIC - UFER Denied IVRS - Inspection :
ITEMS OF 9/9/04 PER RICK HOLLANDER CORRECTED. NEED BOND TO BE POSTED FOR POWER RELEASE
09/09/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) CONDUCTORS TO MEET TAP RULES PER 240.21
2) SECURE PANEL TO WALL
3) MEED MAIN ?? JUMPER & GROUDING ELECTRICAL TROD AT TRANSFORMER
4) NEED REJECTION PINS
5) LABEL EQUIPMENT
6) BOND JUMPERS TUBE SIZED PER 250-102 & 250-66
70 PANEL "LI" TO HAVE MAIN BREAKER
09/03/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*/OK 1-4", 2-2 1/2", 1-1 1/2" PVC FROOM SERVICE TO SUILDING
OK CONDUITS ON WALLS
08/23/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*/NOT READY 1) NEED MAIN BONDING JUMPER AT SERVICE 2) RECIEVED LETTER FOR USE OF M/C CABLE. 3) FINISH PREVIOUS ITEMS
08/20/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :PROTECT M/C CABLE AT STUDS
MISSING "P"RINGS
M/C CABLE LISTED TO TERMINATE, CAN NOT SLEEVE TO A BOX
SUPPORT M/C CABLE WITHIN 12" OF BOXES
BOXES TO HAVE BACK BRACING PER 10F OF PLANS
PLANS CALL FOR CONDUIT PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE