Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T04CM03162
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2004 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
09/10/2004 | ELECTRIC - UFER | Denied | IVRS - Inspection : ITEMS OF 9/9/04 PER RICK HOLLANDER CORRECTED. NEED BOND TO BE POSTED FOR POWER RELEASE |
|
09/09/2004 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) CONDUCTORS TO MEET TAP RULES PER 240.21 2) SECURE PANEL TO WALL 3) MEED MAIN ?? JUMPER & GROUDING ELECTRICAL TROD AT TRANSFORMER 4) NEED REJECTION PINS 5) LABEL EQUIPMENT 6) BOND JUMPERS TUBE SIZED PER 250-102 & 250-66 70 PANEL "LI" TO HAVE MAIN BREAKER |
|
09/03/2004 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :*/OK 1-4", 2-2 1/2", 1-1 1/2" PVC FROOM SERVICE TO SUILDING OK CONDUITS ON WALLS |
|
08/23/2004 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :*/NOT READY 1) NEED MAIN BONDING JUMPER AT SERVICE 2) RECIEVED LETTER FOR USE OF M/C CABLE. 3) FINISH PREVIOUS ITEMS | |
08/20/2004 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :PROTECT M/C CABLE AT STUDS MISSING "P"RINGS M/C CABLE LISTED TO TERMINATE, CAN NOT SLEEVE TO A BOX SUPPORT M/C CABLE WITHIN 12" OF BOXES BOXES TO HAVE BACK BRACING PER 10F OF PLANS PLANS CALL FOR CONDUIT PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE |