Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/22/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/14/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) COMPLETE ITEMS ABOVE AND RECALL |
|
| 09/16/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) HOLDOWNS ?. PROVIDE ATLERNATE HOLDOWNS 2) BLOCK AND NAIL ALL SHEAR PANEL EDGES GARAGE 3) GARAGE #3 SHEAR WALL NOT CONNECTED TO TRUSSES. PROVIDE APPROVED DETAIL 4) HOLDOWNS MUST CORRECT TO FULL LENGTH DBL STUDS, WRONG LOCATIONS 5) STOPPED INSPECTION |
|
| 09/10/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OSB GARAGE SHEARWALL TO CARRY TO ROOF SHEATHING WITH 2 ROWS 8D NAILS AT 6" ON CENTER ( 2 ROWS) 2) INSTALL 'X' BRACING TRUSSES OVER 25' OF RUN 8D AT 6" ON CENTER SPACING NAILS THROUGH OSB SHEATHING INTO BLOCKING BETWEEN TRUSSES AT BEARING EXTERIOR WALLS HOLDOWNS WRONG LOCATIONS; NAILS STAPLES TO BE FLUSH WITH OSB/PLYWOOD 3) REPLACE DAMAGED SHEETS ROOF SHEATHING ( CUTS OUT FOR 2 X 4'S ) 4) STOPPED INSPECTION |