Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 03/29/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ANY VENT WITHIN 10' OF THE MAKE UP AIR. UNIT MUST BE EXTENDED 2' ABOVE EVAP COOLER. COOLER DRAIN SLOPING WRONG DIRECTION. |
|
| 03/13/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE DRAIN LINES FOR A/C AND EVAP COOLER 2) PROVIDE GAS LINE TO FURNACE 3) PROVIDE AUDIBLE AND VISIBLE ALRAMS IN A SUPERVISED LOCATION FOR DUCT SMOKE DETECTOR AS PER IMC 4) EXTEND SEWER VENTS 2' ABOVE MAKE UP AIR UNIT IF WITHIN 10' 5) FIRE WRAP IS OK 6) WHERE AR 1/2" RODS ? |