Permit: T04CM03156

Parcel: 11449036C

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/24/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
03/29/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ANY VENT WITHIN 10' OF THE MAKE UP AIR.
UNIT MUST BE EXTENDED 2' ABOVE EVAP COOLER.
COOLER DRAIN SLOPING WRONG DIRECTION.
03/13/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE DRAIN LINES FOR A/C AND EVAP COOLER
2) PROVIDE GAS LINE TO FURNACE
3) PROVIDE AUDIBLE AND VISIBLE ALRAMS IN A SUPERVISED LOCATION FOR DUCT SMOKE DETECTOR AS PER IMC
4) EXTEND SEWER VENTS 2' ABOVE MAKE UP AIR UNIT IF WITHIN 10'
5) FIRE WRAP IS OK
6) WHERE AR 1/2" RODS ?