Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 05/24/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. KITCHEN RECEPTACLES TO BE GFCI PER 210.8 2. PLEASE VERIFY INTERLOCK FOR OPERATION & LOCATION TO INSPECT MAKE UP. 3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN PANELS & SERVICE EQUIPMENT. 4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING. 5. WHY IS NEUTRAL CONDUCTOR FUSED - A/C? 6. WHERE IS MAINTENANCE RECEPTACLE: 210.63 |