Permit: T04CM03126

Parcel: 140375690


Addresses:

5897 E CEDARBIRD DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/03/2004 FRAMING Approved IVRS - Inspection :*/ 1) LATH OK FOR INTERIOR
12/02/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SEE INSPECTION DATED 12/01/04
2) ELECTRICAL IN LAUNDRY NOT COMPLETE
3) NEXT FAILURE WILL RESULT IN A REFEE
3) NEXT FAILURE WILL RESULT IN A REFEE
12/01/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SGD MISSING, NO LATH AROUND OPENINGS
2) BLOCKS MISSING FOR LATH BACKING AT PATIOS
3) BLOCK OVERFRAMING AND NAIL
4) WINDOW ABOVE MASTER TUB MISSING
5) DWV'S WATER LINES OK
6) TUB BACKING MISSING
7) DBL TOP PLATE AT GARAGE WALL INTO LAUNDRY OVERBORED
8) STRAP DBL TOP PLATE AT W.H. AREA AS PER STRUCTURAL NOTES F & G
9) A.B. MISSING AT SHEAR MASTER BATH
11/30/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) REPLACE OVERBORED DBL TOP PLATE AT GARAGE WALL TO LAUNDRY AND REPLACE STUD
2) DWV'S BEING FILLED WITH WATER
3) WATER LINES CROSSING THROUGH ATTIC ACCESS OPENING
4) STOPPED INSPECTION