Permit: T04CM03119

Parcel: 12604012B


Addresses:

4414 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR 4414 E 2ND ST. WELL NESS CENTER.
04/04/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) A BONDING DEVICE IS NEEDED AT MAIN DISCONNECT 250-94. 2) REJECTION PINS MAY BE NEEDED. 3) LABEL METER & DISCONNECT. * A BOND WILL BE NEEDED FOR TEMP POWER FOR TEST