Permit: T04CM03109

Parcel: 11502171B


Addresses:

534 E ELM ST #02

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/05/2005 FRAMING Approved IVRS - Inspection :*
03/29/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) OVERSPAN ?? STUDS ABOVE HEADERS MIDDLE WALL 24" OC. 2) BLOCK REGISTERS 3 SIDES NAIL PROTECT THROUGHOUT MARKED. PLAN REVISED 3/23 /05 TO USE STUCCO OPTIONS. COMPLETE STUCCO MESH AND RECALL.
03/22/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLAN CALLS FOR STRAPPING BOTH SIDES ALL RAFTERS AT BEARING
2) GROUND ALL METAL ELECTRIC BOXES
3) INSTALL WEDGE FRAMING UNDER RAFTERS TO MAIN MINIMUM 1 1/2" SOLID BEARING ON WALLS AND AT HEADERS WHERE GAPS OCCUR
4) HEADERS TO BE SOLID NOT BOX BEAM TYPE
5) INSTALL PLATE BOLTS WITHIN 12" EACH END BOTTOM PLATES
6) STOPPED INSPECTION
12/27/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
11/17/2004 FRAMING Not ready for Inspection IVRS - Inspection :*