Permit: T04CM03084

Parcel: 114475850

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/17/2004 FRAMING Approved IVRS - Inspection :*
09/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FRONT SHEARWALL NOT DONE
09/14/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) A-35'S NOT INSTALLED PER PLAN OR AS DISCUSSED 2) SEAL GAS PIPE PROFUSION ON WEST SIDE
09/13/2004 FRAMING Partial Approval IVRS - Inspection :*
09/10/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO A-35'S ON SHEAR TRANSFER
09/09/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SUPPORT 3/4 GAS LINE AT 8' ON CENTER 2) SHEARWALL AT BEDROOM MISSING 135 CLIPS AT 12" ON CENTER