Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/08/2005 PLUMBING - FINAL Approved IVRS - Inspection :* NEED (5) IN HOUSE BACKFLOW CERTIFICATIONS. PLEASE LOOK AT H20 TO STEAMER & VERIFY BOTH (2) H20 INLETS ARE PROTECTED BY THE RP BACKFLOW DEVICE.
11/04/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*REMOVE COMBUSTIBLE MATERIAL FROM VENT FROM WATER HEATER AT ROOF PENETRATION AREAS
PROVIDE BTU REQUIEMENT WITH LISTING PLATED FOR CONNECTION OVENS
LOOK BACK THRU ALL NOTES PLEASE
10/27/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*MAKE ALL FIXTURES WATER TIGHT
PROVIDE DRAIN FOR BACKFLOW AT ALL ICE MACHINES N KITCHEN
INSTALL FLUSH VALVE IN MENS RESTROOMS
INSTALL ACCESS ANEL N RESTROOM 246
PROVIDE LONG RADIUS DWV FITTINGS FOR FLOW CONTROL VENT BELOW FLOOD RIM OF FIXTURE
PROVIDE PROOF OF 1" AIRGAP OR PROVIDE BACKFRLOW PROTECTION
PROVIDE SAFETY CABLES FOR GAS EQUIPMENT ON WHEELS
PROVIDE SIGN LOCATING ANSUL VALVE LOCATION IN CEILING
ALL GAS APPLIANCE TO BE CONNECTED CORRECTLY
DRAIN FROM FILTERS TO BE GRAVITY TO TERMINATION
PROVIDE 1" AIR GAP ON ALL INDIRECT DRAIN, NOTE OVER 5' REQUIRE P-TRAP OVER 15' P-TRAP & VENT
SUPPORT WTER HEATER EXPANSION TANKS
PROVIDE ADA LAV COVERS ON LAVS SUPPLY & DRAIN
INSTALL INSULATON ON HOT PIPING IN WATER HEATER AREA
PROVIDE TRAP PRIMER FOR WATER HEATER FLOOR SINK
PROVIDE ALL BACKFLOW CERTIFICATIONS
RUNNING LOW ON INK THIS MAY NOT BE A COMPLETE LIST.
09/27/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* PLEASE CALL IN 3055
CLOSET FLANGES ALL REST ROOMS EXCEPT GANG RESTROOM OK