Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* NEED (5) IN HOUSE BACKFLOW CERTIFICATIONS. PLEASE LOOK AT H20 TO STEAMER & VERIFY BOTH (2) H20 INLETS ARE PROTECTED BY THE RP BACKFLOW DEVICE. | |
| 11/04/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*REMOVE COMBUSTIBLE MATERIAL FROM VENT FROM WATER HEATER AT ROOF PENETRATION AREAS PROVIDE BTU REQUIEMENT WITH LISTING PLATED FOR CONNECTION OVENS LOOK BACK THRU ALL NOTES PLEASE |
|
| 10/27/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*MAKE ALL FIXTURES WATER TIGHT PROVIDE DRAIN FOR BACKFLOW AT ALL ICE MACHINES N KITCHEN INSTALL FLUSH VALVE IN MENS RESTROOMS INSTALL ACCESS ANEL N RESTROOM 246 PROVIDE LONG RADIUS DWV FITTINGS FOR FLOW CONTROL VENT BELOW FLOOD RIM OF FIXTURE PROVIDE PROOF OF 1" AIRGAP OR PROVIDE BACKFRLOW PROTECTION PROVIDE SAFETY CABLES FOR GAS EQUIPMENT ON WHEELS PROVIDE SIGN LOCATING ANSUL VALVE LOCATION IN CEILING ALL GAS APPLIANCE TO BE CONNECTED CORRECTLY DRAIN FROM FILTERS TO BE GRAVITY TO TERMINATION PROVIDE 1" AIR GAP ON ALL INDIRECT DRAIN, NOTE OVER 5' REQUIRE P-TRAP OVER 15' P-TRAP & VENT SUPPORT WTER HEATER EXPANSION TANKS PROVIDE ADA LAV COVERS ON LAVS SUPPLY & DRAIN INSTALL INSULATON ON HOT PIPING IN WATER HEATER AREA PROVIDE TRAP PRIMER FOR WATER HEATER FLOOR SINK PROVIDE ALL BACKFLOW CERTIFICATIONS RUNNING LOW ON INK THIS MAY NOT BE A COMPLETE LIST. |
|
| 09/27/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PLEASE CALL IN 3055 CLOSET FLANGES ALL REST ROOMS EXCEPT GANG RESTROOM OK |