Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/02/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/22/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* WATER TEST GREASE TRAP INSTALL PER PLAN. 1) PROVIDE CITY APPROVED REVISED PLAN OF ?? OF P-12 IN SC?? SHOP 219 OR LETTER FROM ARCH. OR ENGINEER STATING THIS ALTERNATE HAS NOT BEEN TAKEN. PER RED LINE DRAWING ON SITE. WITNESS TO MANHOLE #2 TO BUILDING #4 6" SEWER TEST 4 PSI OK. FOR BUILDING #1 PERMIT.
03/21/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* 3" T/K H20 STUBBED UP AND OUT AT NORTH WEST CORNER 100 PSI AIR TEST PARTIAL APP
03/15/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* WATER TEST WASTE & VENT UNDERGROUND FROM 2-WAY CLEANOUT ON EAST SIDE THRU BUILDING AS HIGHLIGHTED AND INITALED ON PLAN. WATER TEST GREASE WASTE FROM K-31 TO 5' FROM GREASE TRAP 2" VENT IS STUBBED UP & OUT FOR TRAP IN NORTH WALL. 1) NEED TO SEE GREASE TRAP INSTALL WITH VENT & CONNECTION TO BUILDING SEWER.
01/07/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/WATER TEST 4" BUILDING DRAIN FROM 2-WAY CLEANOUT UP STREAM TO P-8, RESTROOMS 212 & 214, MAKEUP 215 & 216 PER HIGHLIGHTED & INITALED PLAN IN TRAILER