Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :*. 1) CEILING GRID WIRES THAT SLOPE MORE THAN LIB REQUIRE COUNTER SLOPING WIRES IN FACULTY DINING AND KITCHEN 2) FOOD SERVICE, BOOK STORE AND OTHER SMALL ROOMS OK 3) OK TO SET TILE IF YOU LEAVE A FEW OUT SO I CAN SEE NEW WIRES |
|
| 10/19/2005 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/23/2005 | BUILDING ABOVE CEILING | Partial Approval | FROM STAGE SOUTH OK TO SET CIEL TILE. 1) CAULK PENETRATIONS IN FIVE BARIER AT 3 PLACES NOTED. IVRS - Inspection :* | |
| 09/01/2005 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* ALL HARD LID FRAMING OK TO COVER |
|
| 08/11/2005 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO ROCK HARD LIDS SOUTH OF MATCH LINE |