Permit: T04CM02992

Parcel: 140376400


Addresses:

6938 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/16/2004 FRAMING Approved IVRS - Inspection :*
11/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/12/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ARMAFLEX NOT REPAIRED
2) B-VENTS HAVE STILL COMBUSTIBLES TOUCHING
3) T & P LINE NOT NAILED PROTECTED
4) NEED PLUMBING REVISION, BEFORE HOUSE IS INSULATED ASKED FOR ON 8/13/04
11/10/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE
2) NAIL PROTECT WATER LINES AT MASTER BATH
3) REPAIR ARMAFLEX
4) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT B-VENT
5) DWV'S AND WATER LINES OK
6) NAIL PROTECT T & P LINE
11/09/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) CANCELLED ON SITE BY JAMES
11/08/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FIREBLOCK MISSING AT STAIR
2) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE
3) FIXTURE BOXES NOT GROUNDED
4) REPAIR ARMAFLEX
5) PROVIDE 1" CLEARANCE AT WATER HEATER B-VENT
6) NO TEST ON DWV'S
7) MOVE ELECTRIC WIRES AWAY FROM GUSSETT PLATES
8) NAIL PROTECT ENTIRE T & P LINE