Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/15/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/12/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ARMAFLEX NOT REPAIRED 2) B-VENTS HAVE STILL COMBUSTIBLES TOUCHING 3) T & P LINE NOT NAILED PROTECTED 4) NEED PLUMBING REVISION, BEFORE HOUSE IS INSULATED ASKED FOR ON 8/13/04 |
|
| 11/10/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 2) NAIL PROTECT WATER LINES AT MASTER BATH 3) REPAIR ARMAFLEX 4) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT B-VENT 5) DWV'S AND WATER LINES OK 6) NAIL PROTECT T & P LINE |
|
| 11/09/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) CANCELLED ON SITE BY JAMES | |
| 11/08/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FIREBLOCK MISSING AT STAIR 2) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE 3) FIXTURE BOXES NOT GROUNDED 4) REPAIR ARMAFLEX 5) PROVIDE 1" CLEARANCE AT WATER HEATER B-VENT 6) NO TEST ON DWV'S 7) MOVE ELECTRIC WIRES AWAY FROM GUSSETT PLATES 8) NAIL PROTECT ENTIRE T & P LINE |