Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) NOTE OF RECORD: TWO OUTLETS UNDER BREAKFAST BAR HAVE BEEN JUNCTIONED OFF (BLANKED OUT) |
|
| 01/12/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE JUNCTION BOX FOR DRYER CIRCUIT, EXTENDED (SPLICED) 2) GAS CARD ISSUED FOR SYSTEM START UP. CANNOT OCCUPY HOME UNTIL FINAL IS APPROVED |
|
| 01/11/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/1)PAINT IRRIGATION PVC 2)FRONT OF HOUSE NEEDS 6" CLEARANCE FROM WEEP SCREED? TO FINAL GRADE 3)NO PLAN ON JOB SITE 4)EAST SIDE YARD NOT GRADED |
|
| 01/10/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS 2) PREVIOUS INSPECTION RESULTS NOT ON SITE 3) SPECIAL INSPECTION REPORTS NOT COMPLETE |
|
| 01/07/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) B-VENT REQUIRES 1" CLEARANCE FROM COMBUSTIBLES 2) SECONDARY PAN HAS CONST. DEBRIS IN IT 3) NO POST TENSION TAG 4) SCREEN MISSING AT WAHSER DRAIN 5) FRONT GRADING NOT COMPLETE 6) CHECK KITCHEN GFCI 7) REST OF HOUSE OK |