Permit: T04CM02991

Parcel: 140376750


Addresses:

6935 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/22/2004 FRAMING Approved IVRS - Inspection :*
11/19/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) FRAMING WILL BE APPROVED , WHEN ALL TRADES ARE COMPLETE
2) ELECTRIC INTERMEDIATE WILL BE APPROVED WHEN GROUND ROD SYSTEM FOR UFER IS INSTALLED
3) NAIL PROTECT DRYER VENT
4) OK TO INSULATE
11/18/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PROVIDE GROUND ROD SYSTEM FOR UFER
2) PANEL NEEDS 36" CLEARANCE FROM WINDOW
3) COACH LIGHT FIXTURE BOX MISSING GROUND SCREW
4) REPLACE 2 X 6 STUD AT KITCHEN WALL
5) NAIL PROTECT ELECTRIC AT KITCHEN
6) CLIP STUDS AT GLB STAIRS
7) NAIL PROTECT DRYER VENT
8) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT B-VENTS
9) FIRE BLOCK MECHANICAL CHASES INTO ATTIC
10) STOPPED INSPECTION