Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/01/2004 | EXT METAL CLIPS/EXT SHEATHING | Cancelled | CANCELLED PER LOURDES OF K.B. HOMES | |
| 09/29/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) HOLDOWN EAST NOT NAILED 2) WIND BRACE REQUIRES 2 NAILS AT END 3) OVERSPANS UNDER WINDOW SILLS EAST SIDE 4) VENT MISSING WEST SIDE 5) KING STUD EACH SIDE OF S.G.D. MISSING 6) NAIL PROTECT PLUMBING FROM OUTSIDE 7) CHECK EDGE NAILING 8) CLIP GIRDER 9) CHECK ROOF FOR NAILING |