Permit: T04CM02975

Parcel: 106051160


Addresses:

815 W THURBER RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/06/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) RE-INSPECT
07/02/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MOUNTING SUB-PANEL WITH DRYWALL SCREWS NOT ALLOWED MINIMUM 1/4" SCREW REQUIRES 2) GFCI ELECTRIC OUTLETS REQUIRED WITHIN 24" OF BOTH SIDES OF KITCHEN SINK THEN EVERY 48" THERE AFTER 3) CONVENIENCE OUTLETS NOT ALLOWED UNDER COUNTER TOP WITH 6" OR MORE OVERHANG 4) PENSULA REQUIRED AN OUTLET GFCI 5) WALLS GREATER THAN 24" REQUIRE A CONVENIENCE OUTLET 6) BEDROOM WINDOW DOES NOT HAVE 5'-0" EGRESS