Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) RE-INSPECT | |
| 07/02/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MOUNTING SUB-PANEL WITH DRYWALL SCREWS NOT ALLOWED MINIMUM 1/4" SCREW REQUIRES 2) GFCI ELECTRIC OUTLETS REQUIRED WITHIN 24" OF BOTH SIDES OF KITCHEN SINK THEN EVERY 48" THERE AFTER 3) CONVENIENCE OUTLETS NOT ALLOWED UNDER COUNTER TOP WITH 6" OR MORE OVERHANG 4) PENSULA REQUIRED AN OUTLET GFCI 5) WALLS GREATER THAN 24" REQUIRE A CONVENIENCE OUTLET 6) BEDROOM WINDOW DOES NOT HAVE 5'-0" EGRESS |