Permit: T04CM02973

Parcel: 140230750

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/03/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 3) OK FOR DRY WALL UPON BLDG INSPECTORS APPROVAL.
03/01/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NOT INSTALLED PER PLAN. PLAN CALLS FOR COPPER WATER PIPING. NO PROVISION MADE FOR INSULATION ON HOT WATER PIPING. NO INDIVIDUAL CONTROLS ON TUB AND SHOWER VALVES
2) IF DRAIN WASTE AND VENT WAS INSTALLED PER ISOMETRIC, WET VENTED SECTIONS ARE UNDER SIZED, IF NOT INSTALLED PER PLAN, NO RED LINES ON SITE
3) HORIZONTAL VENT PIPING OVER HEAD TO BE SUPPORTED